7 Day Programmable
4 Time Periods per Day
Product Features:
Programs
- 7-Day, 5+1+1 day or 1-day programmable with up to 3 occupied and 1 unoccupied periods per day
- Random start ensures staggered equip. starts
- Standard holiday mode or 365-day holiday programming with PSPAC-PWF Wi-Fi module
Staging
- Independently adjustable staging deadbands for all stages of heating and cooling (1° - 10° F)
- Independently adjustable staging timers for all stages of heating and cooling (1 - 60 mins)
- Adjustable staging turnoffs, i.e. de-energize 2nd stage at deadband or keep active until setpoint
Security
- Setpoint limiting
- Keypad lock
- Lock box security with PSPAC-LR locking ring
- Secure API (http or https) w/ PSPAC-PWF module
Fan Ops
- Smart fan operation runs continuous during Occupied; only for heat or cool during Unoccupied
- Smart recovery auto-adjusts Occ 1 start time to meet setpoint by programmed start time
Sensors
- Outdoor sensor ready with Hi/Low readouts for the day
Alerts
- Dry contact input for twist timers, etc. or...
- Condensate overflow warning systems – lockout compressor with display message
- FDD (Equipment Fault Protection) notification
Certs
- Title 24 compliant with PSPAC-PWF Wi-Fi module
- Energy Star certified with PSPAC-PWF Wi-Fi module
Terminal
Designations
Designations
Product
Specificatons
Specificatons
Cross
Reference
Reference
FREE Contractor
Branding
Branding
Terminal Designations | |
---|---|
R | 24 VAC Return |
G | Fan Relay |
W1/O/B | 1st Stage Heat Circuit or reversing valve |
W2 | 2nd Stage Heat Circuit |
Y1 | 1st Stage Compressor Relay |
Y2 | 2nd Stage Compressor Relay |
W3 | 3rd Stage Heat Circuit |
C | 24 VAC Common |
Outdoor Sensor | Outdoor Sensor Connections |
Dry Contact | Dry Contact Connections |